1 EN 54-16 Compliant Installation of Voice Alarm Systems

Download Report

Transcript 1 EN 54-16 Compliant Installation of Voice Alarm Systems

1
EN 54-16
Compliant Installation of
Voice Alarm Systems
T. Kranz TOA Germany
When does EN54-16 Apply?
2
Construction Products Directive CPD
CPD: EN54 is mandatory for fire detection and
alarm systems in all EU member states
 2008: issue of two new parts of EN54
 Part 16: voice alarm systems
End of co-existence period*: March 2011
 Part 24: loudspeakers for voice alarm systems
End of co-existence period*: April 2011
* End of co-existence period: conflicting national
standards must be withdrawn
T. Kranz TOA Germany
When does EN54-16 Apply?
System depending
 EN 54-16 must be applied
• When the voice alarm system is controlled by the
fire detection system
 Application not necessary
• When the voice alarm system is a stand-alone
system (triggered manually) or
• controlled by others that fire detection systems
 When must voice alarm be applied?
• National requirements
T. Kranz TOA Germany
3
Approved VA Systems
4
Certification
 The voice alarm system must be certified on
EN54-16 by a notified body
• Notified bodies can be found on the EU Web
sites
 Certificate of the notified body contains
• Certificate number
• Approved system components
• Approved options
T. Kranz TOA Germany
Approved VA Systems
Indication of Approval
 Certificate number
• at least on one main part of the VA system
• in the accompanied documents
 Applicable options
• in the accompanied documents
T. Kranz TOA Germany
5
6
EN 54-16 Compliant Design
Access Levels
Mandatory Function
Mandatory Indications
T. Kranz TOA Germany
Access Levels
Access Level 1
 Public areas or
 Areas with unrestricted access for
persons having a general responsibility
for safety supervision
• E.g. in a technical room
 Manual controls shall be accessible
without special procedures
• E.g. not by opening a door
T. Kranz TOA Germany
7
Access Levels
Access Level 2
 Access restricted by special procedures
• Access by
- mechanical key (locked technical room)
- code of at least 3 sequential operations
- access cards
 Access for Persons
• with specific responsibility for safety and
• Authorised and trained on operating
T. Kranz TOA Germany
8
Mandatory Indications
9
Must be in Access Level 1 always
 VA condition, especially EMERGENCY
• Indication on a remote microphone by programmed
fault receipt (acknowledge) button (SX: on SM)
 General Fault
• Indication on a remote microphone by programmed
fault receipt (acknowledge) button (SX: on SM)
 System Fault
• Indication on a remote microphone by programmed
fault receipt (acknowledge) button (SX: on SM)
T. Kranz TOA Germany
Mandatory Indications
10
Must be in Access Level 1 always
 Fuse Rupture
• Indication on a remote microphone by programmed
fault receipt (acknowledge) button for all amps
 Fault in Signal Path between System components
• Only for SX-2000: indication by programmed fault
receipt (acknowledge) button
 Earth Leakage
• For outgoing wires (e.g. speaker lines, microphones)
• Only necessary if not implemented in other fault
T. Kranz TOA Germany
Mandatory Functions
Must be in Access Level 1 always
 Lamp Test (Button)
• To test the mandatory indications
 Fault Acknowledge (Button)
• In TOA VA systems always combined with
fault indications
T. Kranz TOA Germany
11
Options
12
Mandatory Indications
 Faults in VA Zones
• One fault indicator per VA zone
 Fault in the connection to the fire detection
system
• A separate indicator must be provided
T. Kranz TOA Germany
Options
13
Access Level









T. Kranz TOA Germany
Manual Silencing
Manual Reset of the VA condition
VA condition output
VA manual control
Emergency microphones
Redundant power amplifiers
Audible warning of VA condition
VA manual control
Phased evacuation
2
2
n.a.
2
2
n.a.
1, 2
2
2
Options
14
Available on TOA VA Systems
 Manual Silencing
SX, VX
• Button on emergency microphone
• VX: acivating dummy text (silence)
• SX: stopping emergency pattern or sequence
 Manual Reset of the VA condition
SX, VX, VM
• Emergency reset button
 VA condition output
SX, VX, VM
• Control output
 VA manual control
SX, VX, VM
• Manual assignment of emergency messages to
emergency zones
T. Kranz TOA Germany
Options
15
Available on TOA VA Systems
 Emergency microphones
VX, VX, VM
• Fireman microphone, emergency microphone (VX, SX)
 Redundant power amplifiers
SX, VX, VM
• Standby amplifiers
 Audible warning of VA condition
VM
• Buzzer tone when emergency was activated
 Phased evacuation
SX
• When phases can be controlled manually or by fire
detection system