Practice Code Look Up
Download
Report
Transcript Practice Code Look Up
Copyright 2008 Ted "Smitty" Smith
Left click on the presentation ICON
located at the bottom of the slide directory
to the left of the this slide.
Each slide will transition to the correct
answer automatically in 2:00 minutes. The
correct answer will transition in 10 seconds.
You may also left click on the slide to
manually transition.
Do not worry about writing down the
correct answer for now. You will have the
opportunity to do that at the end of the
two minute drill
Good luck
Remember to start the slide show to
activate the timer.
Copyright 2005 Ted "Smitty" Smith
This
drill is a mixture of
calculations and code
look up questions. You
have seen many of
them before. Focus on
time. Try to find all the
answers before the
slide transitions.
Remember do not
worry about writing
down the right answer
for now. When you
reach the end all of
the slides will be
repeated without the
timer so you can take
your time to find the
ones you missed and
write down the correct
answers then.
Click on the slide to
proceed.
Copyright 2005 Ted "Smitty" Smith
1.
Equipment grounding conductors shall be
permitted to be sectioned within a listed
multiconductor cable, provided the combined
_______________ complies with 250.122.
A. Current and load
B. Voltages of all applied loads
C. Circular mill area
D. None of the above
Copyright 2008 Ted "Smitty" Smith
Circular mill area
310.13
Copyright 2005 Ted "Smitty" Smith
A conductor with insulation marked ZW
will be suitable for use in all:
Wet locations
Hospital operating rooms
House boats
None of the above
Copyright 2005 Ted "Smitty" Smith
Wet locations
Table 310.13(A)
Copyright 2005 Ted "Smitty" Smith
Where more than one calculated or
____________ ampacity could apply for a
given circuit, the lowest value shall be
used.
Determined
Tabulated
Corrected
Derated
Copyright 2005 Ted "Smitty" Smith
Tabulated 310.15(A)(2)
Copyright 2005 Ted "Smitty" Smith
Where bare or covered conductors are
installed with insulated conductors, the
temperature rating of the bare or covered
conductor shall be _____________ for the
purpose of determining ampacity
Equal to the lowest temperature rating of the
insulated conductors
Equal to the highest temperature rating of the
insulated conductors
Equal to the average temperature ratings of the
insulated conductors.
None of the above
Copyright 2005 Ted "Smitty" Smith
Equal to the lowest temperature rating of the
insulated conductors
310.15(B)(3)
Copyright 2005 Ted "Smitty" Smith
A 2 AWG TW conductor is installed in a
location where the ambient
temperature is expected to be 108
degrees F. The temperature correction
factor for conductor ampacity in this
location is _________.
.96
.88
.82
.71
Copyright 2005 Ted "Smitty" Smith
.71
Table 310.16 Bottom, 60c wire at 102
degrees F.
I recommend using a straight edge
when using NEC tables. A clear plastic 6
inch ruler is best.
Copyright 2005 Ted "Smitty" Smith
If the ambient temperature is 30 degrees
C, the minimum insulation that a
conductor must have and still have the
capacity to carry current is __________
60 C
105 C
90 C
Any of these
Copyright 2008 Ted "Smitty" Smith
Any of these
All of these conductors are rated for 30
degrees C
Copyright 2005 Ted "Smitty" Smith
Determine the minimum sized THHN
aluminum conductor that can be
installed to feed a load of 104 amperes
that is located in a freezer that has an
ambient temperature of 22 degrees
Celsius.
1 AWG
2 AWG
3 AWG
1/0 AWG
Copyright 2008 Ted "Smitty" Smith
100 A 1/0 AWG
110.14(c) will require you handle 104 amperes
in the 75 C column, so another two wire sizes will
be required, therefore 1/0.
Copyright 2005 Ted "Smitty" Smith
The ampacity of six-current carrying 10
AWG RHW aluminum conductors in a
raceway in an ambient temperature of
75 degrees F is ___________
›
›
›
›
30A
22A
16A
12A
Copyright 2005 Ted "Smitty" Smith
15.75A
Table 310.16 and 310.15(B)(2)(a)
Copyright 2005 Ted "Smitty" Smith
The ampacity of nine current carrying 10 AWG THW
conductors installed in a 20 inch long raceway is
_________.
› 25A
› 30A
› 35A
› None of these
Copyright 2005 Ted "Smitty" Smith
35A
Bundle factors do not apply to raceways
that are 24 inches in length or less.
Copyright 2005 Ted "Smitty" Smith
Enclosures for switches or over current devices shall not be
used as junction boxes, auxiliary gutters, or raceways for
conductors feeding through or tapping off to other switches
or over current devices, unless adequate space for this
purpose is provided. The conductors shall not fill the wiring
space at any cross section to more than _______ percent of
the cross-sectional area of the space.
› 20
› 25
› 35
› 40
Copyright 2005 Ted "Smitty" Smith
40
312.8
Copyright 2005 Ted "Smitty" Smith
What is the area in square inches for a 14
AWG RHW without outer covering
conductor?
› 0.0209
› 0.0172
› 0.0252
› 0.0278
Copyright 2005 Ted "Smitty" Smith
0.0209
Table 5, Chapter 9
Copyright 2005 Ted "Smitty" Smith
What is the cross sectional area in square inches for
12 AWG RHH with outer covering conductors?
› 0.0117
› 0.0353
› 0.0252
› 0.0327
Copyright 2005 Ted "Smitty" Smith
0.0353
Table 5, Chapter 9
Copyright 2005 Ted "Smitty" Smith
A 200A feeder installed in Schedule 80
rigid non-metallic conduit has three 3/0
AWG THHN, one 2 AWG THHN and one 6
AWG THHN conductors. What is the
minimum sized raceway required?
2 inch
2.5 inch
3 inch
3.5 inch
Copyright 2005 Ted "Smitty" Smith
2 inch
Copyright 2005 Ted "Smitty" Smith
What size rigid metal nipple is required
for three 4/0 AWG THHN, one 1/0 AWG
THHN and one 4 AWG THHN conductors?
1.5 inch
2 inch
2.5 inch
None of these
Copyright 2005 Ted "Smitty" Smith
1.5 inch
1.239
60% fill based on note 4 to Table 1
Copyright 2005 Ted "Smitty" Smith
What size outlet box is required for one
12/2 NM cable that terminates on a
switch, on 12/3 NM cable that terminates
on a receptacle, and the box has
manufactured internal cable clamps.
› 4 x 1 1/4 square
› 4 x 1 1/2 square
› 4 x 2 1/8 square
› None of these
Copyright 2005 Ted "Smitty" Smith
4 x 2 1/8 Square
Copyright 2005 Ted "Smitty" Smith
Machine screw type fasteners that
engage not less than two and thread
forming machine screws that engage
not less than two threads in the
enclosure may be used to mount
equipment grounding bars, buses and
lugs to enclosures.
› True
› False
Copyright 2005 Ted "Smitty" Smith
True
250.8
Copyright 2005 Ted "Smitty" Smith
What is the net computed demand load for
the air conditioning and heat for a 40 unit
multifamily building that has an air
conditioner ( 3hp, 3.91 kW 230V) and two
baseboard heaters (3 kW) in each unit.
› 160 kW
› 240 kW
› 6 kW
› 5 kW
Copyright 2005 Ted "Smitty" Smith
240 kW
Heat is larger load than A/C
Copyright 2005 Ted "Smitty" Smith
What is the demand load on the main
service entrance of an apartment
complex that is supplied with a 120/208V
single phase service for twelve 3.25 kW
ovens?
10 kW
18 kW
15 kW
20 kW
Copyright 2005 Ted "Smitty" Smith
18 kW
Copyright 2005 Ted "Smitty" Smith
What is the general lighting load for a
dwelling unit with 2,700 square feet of
living space not including open porches,
garages, or unused or unfinished spaces
not adaptable for future use?
›
›
›
›
8100 VA
12600 VA
2700 VA
6480 VA
Copyright 2005 Ted "Smitty" Smith
8100 VA
Copyright 2005 Ted "Smitty" Smith
What is the feeder or service demand for
two 3 kW ranges?
› 3 kW
› 4.8 kW
› 4.5 kW
› 3.9 kW
Copyright 2005 Ted "Smitty" Smith
4.5 kW
Copyright 2005 Ted "Smitty" Smith
If the total demand is 30 kW for a
120/240V dwelling unit, what is the
minimum sized service and feeder
copper conductor size allowed?
4 AWG
3/0 AWG
2 AWG
1/0 AWG
Copyright 2005 Ted "Smitty" Smith
2 AWG
30,000/240= 125A
Table 310.15(B)(6) shows 2 AWG copper
for 125A services
Copyright 2005 Ted "Smitty" Smith
What is the demand on the main service
entrance of a single family dwelling of a
range with a nameplate rating of 13.9
kVA at 240 volts?
› 8000 VA
› 8800 VA
› 9600 VA
› 10000 VA
Copyright 2005 Ted "Smitty" Smith
8800 VA
Table 220.55 Note 1
Copyright 2005 Ted "Smitty" Smith
The disconnecting means for surge
protective devices shall not be
considered a disconnecting means
when determining the maximum
number of handles for the service
disconnecting means.
True
False
Copyright 2005 Ted "Smitty" Smith
True
230.71(A)(2)
Copyright 2005 Ted "Smitty" Smith
Metal enclosures and raceways for service
conductors and equipment shall be
connected to the _______________ system
conductor if the electrical system is
grounded or to the ________________
conductor for electrical systems that are
not grounded.
Grounded/ ungrounded
Grounded/ grounding electrode
Grounding/ grounded
None of the above
Copyright 2005 Ted "Smitty" Smith
Grounded/ Grounding electrode
250.80
Copyright 2005 Ted "Smitty" Smith
Each of the
slides will now
be repeated.
They are not
timed in this
segment. To
change a slide,
click on the side
with your left
mouse button.
Be sure to
physically look
up the answers
in your code
book to improve
your look up
speed and skill.
Copyright 2005 Ted "Smitty" Smith
1.
Equipment grounding conductors shall be
permitted to be sectioned within a listed
multiconductor cable, provided the combined
_______________ complies with 250.122.
A. Current and load
B. Voltages of all applied loads
C. Circular mill area
D. None of the above
Copyright 2008 Ted "Smitty" Smith
Circular mill area
310.13
Copyright 2005 Ted "Smitty" Smith
A conductor with insulation marked ZW
will be suitable for use in all:
Wet locations
Hospital operating rooms
House boats
None of the above
Copyright 2005 Ted "Smitty" Smith
Wet locations
Table 310.13(A)
Copyright 2005 Ted "Smitty" Smith
Where more than one calculated or
____________ ampacity could apply for a
given circuit, the lowest value shall be
used.
Determined
Tabulated
Corrected
Derated
Copyright 2005 Ted "Smitty" Smith
Tabulated 310.15(A)(2)
Copyright 2005 Ted "Smitty" Smith
Where bare or covered conductors are
installed with insulated conductors, the
temperature rating of the bare or covered
conductor shall be _____________ for the
purpose of determining ampacity
Equal to the lowest temperature rating of the
insulated conductors
Equal to the highest temperature rating of the
insulated conductors
Equal to the average temperature ratings of the
insulated conductors.
None of the above
Copyright 2005 Ted "Smitty" Smith
Equal to the lowest temperature rating of the
insulated conductors
310.15(B)(3)
Copyright 2005 Ted "Smitty" Smith
A 2 AWG TW conductor is installed in a
location where the ambient
temperature is expected to be 108
degrees F. The temperature correction
factor for conductor ampacity in this
location is _________.
.96
.88
.82
.71
Copyright 2005 Ted "Smitty" Smith
.71
Table 310.16 Bottom, 60c wire at 102
degrees F.
I recommend using a straight edge
when using NEC tables. A clear plastic 6
inch ruler is best.
Copyright 2005 Ted "Smitty" Smith
If the ambient temperature is 30 degrees
C, the minimum insulation that a
conductor must have and still have the
capacity to carry current is __________
60 C
105 C
90 C
Any of these
Copyright 2008 Ted "Smitty" Smith
Any of these
All of these conductors are rated for 30
degrees C
Copyright 2005 Ted "Smitty" Smith
Determine the minimum sized THHN
aluminum conductor that can be
installed to feed a load of 104 amperes
that is located in a freezer that has an
ambient temperature of 22 degrees
Celsius.
1 AWG
2 AWG
3 AWG
1/0 AWG
Copyright 2008 Ted "Smitty" Smith
100 A 1/0 AWG
110.14(c) will require you handle 104 amperes
in the 75 C column, so another two wire sizes will
be required, therefore 1/0.
Copyright 2005 Ted "Smitty" Smith
The ampacity of six-current carrying 10
AWG RHW aluminum conductors in a
raceway in an ambient temperature of
75 degrees F is ___________
›
›
›
›
30A
22A
16A
12A
Copyright 2005 Ted "Smitty" Smith
15.75A
Table 310.16 and 310.15(B)(2)(a)
Copyright 2005 Ted "Smitty" Smith
The ampacity of nine current carrying 10 AWG THW
conductors installed in a 20 inch long raceway is
_________.
› 25A
› 30A
› 35A
› None of these
Copyright 2005 Ted "Smitty" Smith
35A
Bundle factors do not apply to raceways
that are 24 inches in length or less.
Copyright 2005 Ted "Smitty" Smith
Enclosures for switches or over current devices shall not be
used as junction boxes, auxiliary gutters, or raceways for
conductors feeding through or tapping off to other switches
or over current devices, unless adequate space for this
purpose is provided. The conductors shall not fill the wiring
space at any cross section to more than _______ percent of
the cross-sectional area of the space.
› 20
› 25
› 35
› 40
Copyright 2005 Ted "Smitty" Smith
40
312.8
Copyright 2005 Ted "Smitty" Smith
What is the area in square inches for a 14
AWG RHW without outer covering
conductor?
› 0.0209
› 0.0172
› 0.0252
› 0.0278
Copyright 2005 Ted "Smitty" Smith
0.0209
Table 5, Chapter 9
Copyright 2005 Ted "Smitty" Smith
What is the cross sectional area in square inches for
12 AWG RHH with outer covering conductors?
› 0.0117
› 0.0353
› 0.0252
› 0.0327
Copyright 2005 Ted "Smitty" Smith
0.0353
Table 5, Chapter 9
Copyright 2005 Ted "Smitty" Smith
A 200A feeder installed in Schedule 80
rigid non-metallic conduit has three 3/0
AWG THHN, one 2 AWG THHN and one 6
AWG THHN conductors. What is the
minimum sized raceway required?
2 inch
2.5 inch
3 inch
3.5 inch
Copyright 2005 Ted "Smitty" Smith
2 inch
Copyright 2005 Ted "Smitty" Smith
What size rigid metal nipple is required
for three 4/0 AWG THHN, one 1/0 AWG
THHN and one 4 AWG THHN conductors?
1.5 inch
2 inch
2.5 inch
None of these
Copyright 2005 Ted "Smitty" Smith
1.5 inch
1.239
60% fill based on note 4 to Table 1
Copyright 2005 Ted "Smitty" Smith
What size outlet box is required for one
12/2 NM cable that terminates on a
switch, on 12/3 NM cable that terminates
on a receptacle, and the box has
manufactured internal cable clamps.
› 4 x 1 1/4 square
› 4 x 1 1/2 square
› 4 x 2 1/8 square
› None of these
Copyright 2005 Ted "Smitty" Smith
4 x 2 1/8 Square
Copyright 2005 Ted "Smitty" Smith
Machine screw type fasteners that
engage not less than two and thread
forming machine screws that engage
not less than two threads in the
enclosure may be used to mount
equipment grounding bars, buses and
lugs to enclosures.
› True
› False
Copyright 2005 Ted "Smitty" Smith
True
250.8
Copyright 2005 Ted "Smitty" Smith
What is the net computed demand load for
the air conditioning and heat for a 40 unit
multifamily building that has an air
conditioner ( 3hp, 3.91 kW 230V) and two
baseboard heaters (3 kW) in each unit.
› 160 kW
› 240 kW
› 6 kW
› 5 kW
Copyright 2005 Ted "Smitty" Smith
240 kW
Heat is larger load than A/C
Copyright 2005 Ted "Smitty" Smith
What is the demand load on the main
service entrance of an apartment
complex that is supplied with a 120/208V
single phase service for twelve 3.25 kW
ovens?
10 kW
18 kW
15 kW
20 kW
Copyright 2005 Ted "Smitty" Smith
18 kW
Copyright 2005 Ted "Smitty" Smith
What is the general lighting load for a
dwelling unit with 2,700 square feet of
living space not including open porches,
garages, or unused or unfinished spaces
not adaptable for future use?
›
›
›
›
8100 VA
12600 VA
2700 VA
6480 VA
Copyright 2005 Ted "Smitty" Smith
8100 VA
Copyright 2005 Ted "Smitty" Smith
What is the feeder or service demand for
two 3 kW ranges?
› 3 kW
› 4.8 kW
› 4.5 kW
› 3.9 kW
Copyright 2005 Ted "Smitty" Smith
4.5 kW
Copyright 2005 Ted "Smitty" Smith
If the total demand is 30 kW for a
120/240V dwelling unit, what is the
minimum sized service and feeder
copper conductor size allowed?
4 AWG
3/0 AWG
2 AWG
1/0 AWG
Copyright 2005 Ted "Smitty" Smith
2 AWG
30,000/240= 125A
Table 310.15(B)(6) shows 2 AWG copper
for 125A services
Copyright 2005 Ted "Smitty" Smith
What is the demand on the main service
entrance of a single family dwelling of a
range with a nameplate rating of 13.9
kVA at 240 volts?
› 8000 VA
› 8800 VA
› 9600 VA
› 10000 VA
Copyright 2005 Ted "Smitty" Smith
8800 VA
Table 220.55 Note 1
Copyright 2005 Ted "Smitty" Smith
The disconnecting means for surge
protective devices shall not be
considered a disconnecting means
when determining the maximum
number of handles for the service
disconnecting means.
True
False
Copyright 2005 Ted "Smitty" Smith
True
230.71(A)(2)
Copyright 2005 Ted "Smitty" Smith
Metal enclosures and raceways for service
conductors and equipment shall be
connected to the _______________ system
conductor if the electrical system is
grounded or to the ________________
conductor for electrical systems that are
not grounded.
Grounded/ ungrounded
Grounded/ grounding electrode
Grounding/ grounded
None of the above
Copyright 2005 Ted "Smitty" Smith
Grounded/ Grounding electrode
250.80
Copyright 2005 Ted "Smitty" Smith