Transcript ppt – RELAI FREKUENSI
DOK - IBA
DOK - IBA
RELAI FREKUENSI
BESARAN INPUT DARI RELAI FREKUENSI ADALAH TEGANGAN YANG DIAMBIL DARI TRAFO TEGANGAN [ PT ] RELAI INI MEMONITOR BESARNYA FREKUENSI SISTEM .
1. RELAI FREKUEN SI KURANG [ UFR ]
MEMBANDINGKAN FREKUENSI SISTEM DENGAN FREKUENSI SETTINGNYA .
BILA FREKUENSI SISTEM LEBIH KECIL ATAU SAMA DENGAN FREKUENSI SETTING MAKA RELAI AKAN KERJA
2. RELAI FREKUENSI LEBIH
BILA FREKUENSI SISTEM LEBIH BEAR ATAU SAMA DENGAN FREKUENSI SETTING MAKA RELAI AKAN KERJA .
DOK - IBA
FUNGSI / APLIKASI UFR
1. DIPASANG PADA PENYULANG TM , UNTUK LOAD SHEDDING SECARA OTOMATIS BILA TERJADI PENURUNAN FREKUENSI SIATEM , AKIBAT KEHILANGAN DAYA PEMBANGKIT .
ADA 6 TAHAP PENYETELAN RELAI UFR DI PENYULANG 20 KV PLN YAITU 48,8 – 48,3 Hz 2. DIPASANG DI PEMBANGKIT ,UNTUK MEMISAHKAN PEMBANGKIT DARI SISTEM INTERKONEKSI, BILA TERJADI GANGGUAN PADA SISTEM [ ISLANDING SYSTEM ] DILENGKAPI DENGAN UVR .
FUNGSI / APLIKASI OFR
DIPASANG DI PEMBANGKIT SEBAGAI PENGAMAN KECPATAN LEBIH [ OVERSPEED ]
DOK - IBA
Prinsip kerja elektrodinamik
48 50 52 R1 f C V R2 f
Relai frekuensi dengan asas induksi
DOK - IBA V V T1 T2
T1
T1
T2
T2 1 2
DOK - IBA MFVU
T 1 0 .
0 .
0 .
0 .
0 .
0 .
sec f 1 1 T 1 Hz T 2 0 .
0 .
0 .
0 .
0 .
0 .
sec f 2 1 T 2
Hz
MFVU210CA00045
f1 f2 f1 ON ON Pu:do 1:1 0.05
0,1 0,2 0,2
t1 (0,1 sec
0,5
)
1 2 2 5 10
f1 f2 OFF OFF f2:f1 0 0 0 0 0 0 0 0 0 0 0,05 0.1
0,2 0,2 0,5 1 2 2 5 10 Vx=110V= 0 0 0 0 0 0 0 0 0 0
t2 (0,1 ) sec
f1 f2 Test Reset
28 27 26 V V TEST V> 1 & 2 & 17 18 V V= + 0V t1 t2 T1 T2
T1
T1
T2
T2 1 2 RESET SET f2:f1 f2:f2
R L 1 2
SET RESET PU DO SET RESET
R L 2 2
RESET DIAGRAM INTERNAL RELAI FREKUENSI TIPE MFVU 21 GEC RL1-1 f1 RL1-2 f2 RL2-1 RL2-2 2 4 6 1 3 5 9 11 13 10 12 14 DOK - IBA
PT
f1
f2 PT V= t1 t2 BUS 20 KV PENGAWATAN
+
110V 27 28 17 18 + MFVU 21 1 3 9 11 52TC 52a 52TC 52a TRIP PMT 1 TRIP PMT 2 DOK - IBA
PORTABLE TESTSET TIPE FTS 300 EIL 10 12 13 Keterangan Gambar : 1.
2.
3.
4.
5.
6.
7.
8.
Power Input Connection Main Power Switch Function Switch AC signal Output Output Voltage Control Output Voltage Meter Frequency Range Switch Frequency adjust Control 9.
Frequency meter / Timer 10. Contact / DC power terninal 11. DC Power Supplay Control 12. Contact mode select switch 13. Contact status Indicator 14. Target current control / range switch 15. DC Ammeter 15 14 + CONTACT
-
A 1 SUPPLY 220V 7 FTS 300 EIL NORM. FREQ .
FAULT FREQ.
ON OFF 2 3 9 250V 125V 48V OFF V OUTPUT 11 8 6 5 4 DOK - IBA
FUNGSI ALAT KONTROL PADA PANEL DEPAN ALAT UJI FTS 300 DOK - IBA 1. Power Input Connection Menghubungkan power cord untuk mendapatkan power input pada alat uji ( suplai 220V).
2. Main Power switch Mengontrol input power dan juga sebagai pemutus dalam hal hubung singkat atau gangguan. Untuk menunjukan bahwa alat uji dienergis maka lampu akan menyala.
3. Function Switch Memilih kondisi kerja dari alat uji 4. AC signal Output Memberikan output AC signal dari alat uji 5. Output Voltage control Mengatur besarnya AC output signal. Knob “Output control” terdiri dari dua potensio konsentris, knob luar mengatur besarnya tegangan normal, dan knob dalam mengtur besarnya tegangan gangguan. Tombol Read Fault Voltage memungkinkan tegangan gangguan ada dalam kondisi Set Fault sebelum diswitch ke posisi Test 6. Output Voltage meter Memonitor besarnya tegangan AC signal yang ada pada signal output.
DOK - IBA 7. Frquency range switch Untuk memilih output rentang frekuensi 40 – 70 Hz atau 360 – 440 Hz 8. Frequency Adjust control Potensiometer dengan 15 posisi yang mana mengatur frekuensi normal dan gangguan 9. Frequency meter / Timer Untuk menampilkan frekuensi normal / frekuensi gangguan atau waktu , tergantung pada kondidsi kerja / mode dari alat uji. Dibawah meter ditunjukan 2 buah lampu Led yang ditandai dengan “Hertz” dan “Second”.
10. Contact DC power supplay terminals Terminal merah dan kuning digunakan untuk memonitor status dray contact atau scr dalam kondisi Normal ,Set Fault dan Test. Penutupan contact ditandai oleh Led dari kontak closed. Dalam kondisi Test penutupan kontak dapat digunakan untuk menyetop Timer.
11. Dc Power Supplay Control Memilih tegangan output Dc yang ada pada terminal merah dan hitam. Tiga jenis tegangan yang tersedia yaitu 48V, 125V dan 250V sesuai kebutuhan relai. Indikator On/Reset adalah suatu Led oranye akan menyala bila tegangan ada. Supplay diproteksi terhadap beban lebih,dan dapat direset dengan menekan tombol tekan (Led).
DOK - IBA 12. Contact Mode Select Switch Untuk menentukan apakah timbul atau tidak hubung pendek pada terminal merah dan kuning, dan akan menyetop timer dalam kondisi Test. Dengan memilih salah satu kontak normally open atau close untuk memonitor test penundaan waktu.
13. Contact status Indicator Led yang menyala untuk menunjukan suatu hubung pendek pada terminal merah dan kuning.
14. Target Current Control/Range Switc Knob luar adalah suatu saklar yang memilih range dari Ammeter DC yang diinginkan yaitu 0,3 atau 3 A. Knob dalam adalah suatu potensio yang mengtur besarnya arus DC dalam kondisi Target.
15. DC Ammeter Memonitor arus dari internal DC supplay dalam kondisi Normal , Set Fault dan Test ,dan mengukur besarnya arus DC pada terminal merah dan kuning dalam kondisi Target.
PENGUJIAN INDIVIDUAL RELAI FREKUENSI KURANG TIPE MFVU 21 GEC – TEST SET FTS 300 DOK - IBA 1. TUJUAN Setelah melaksanakan pengujian siswa diharapkan dapat mengukur: 1. pickup / drop off frequency 2. waktu kerja relai frekuensi 2. ALAT UJI / RELAI 1. Frequency Test Set model FTS 300 (EIL) 2. Relai frekuensi tipe MFVU 21 GEC 3. RANGKAIAN PENGUJIAN 1. Rangkai lah rangkaian pengujian ( lihat gambar pengujian ) 2. Hubungkan sumber tegangan 220V ke alat uji 3. Posisikan kontrol ( tombol, saklar, alat ukur ) dari alat uji FTS 300 sebagai berikut :
RANGKAIAN PENGUJIAN RELAI FREKUENSI TIPE MFVU 21 GEC FTS 300 EIL + CONTACT
-
SUPPLY 220V A NORM. FREQ .
FAULT FREQ.
ON OFF 250V 125V 48V OFF V OUTPUT 1 3 9 11
-
+ 17 18 MFVU 21 GEC 26 27 28 DOK - IBA PORTABLE TESTSET TIPE FTS 300 EIL RELAI YANG DIUJI
DOK - IBA Kontrol Posisi Main Power switch . . . . . . . .. . . . . . Off Function Switch . . . . . . . . . . . . . Normal Output Voltage adjust control . . . . . . . Putar penuh kekiri Frequency range switch . . . . . . . . . . 40 – 70 Hz Frequency adjust control . . . . . . . . . Mid range Contact mode select switch . . . . . . . . NO (open) Target current range switch . . . . . . . . Sesuai yang diinginkan Target current control . . . . . . . . . . . Putar penuh kekiri DC power supply . . . . . . . . . . . . . . Sesuai yang diinginkan 4. PENGUJIAN PICK UP / DROP OFF FREQUENCY 1. Hidupkan alat uji ( Main power switch pada posisi on ) 2. Putar Output Voltage control ke kanan sampai Voltmeter menunjuk tegangan input nominal relai (100V) 3. Atur normal frequency control sampai frekuensi meter menunjuk harga rated dari normal frekuensi 4. Atur normal frequency control sampai relai mulai pick up ( indikator kontak menyala ) dan naikan frekuensi sampai indikator kontak padam ( reset ) 5. Cata kedua besaran ini , dan ulangi percobaan ini untuk output tegangan yang laian .
DOK - IBA 5. PENGUJIAN WAKTU KERJA RELAI 1. Atur nominal frequency control sehingga frekuensi meter menunjuk harga rated dari normal frekuensi (50Hz) 2. Putar Function swicth ke posisi set fault 3. Atur Fault frequency control sehingga frekuensi meter menunjuk frekuensi yang diinginkan 4. Tekan tombol read voltage control dan atur tegangan gangguan dengan mengatur output voltage control 5. Putar Function switch pada posisi Test maka frekuensi meter akan berubah menjadi Timer (akan mencatat waktu kerja relai ) 6. Ulangi pengujian diatas untuk setting waktu yang lain atau frekuensi gangguan yang lain.
7. Matikan alat uji dan lepas kabel kontrol .
110V DC AUX. SUPPLY UE+ UE- E 29 33 31 37 41 39 45 + NF92 1 3 7 9 UE- UE+ 45 1 3
7 9
UE- UE+ 45
1 3 5 13 7 9 + _ + FC 95 - 22 29 33 31
37 41 39
45
29 33 31 37 41 39 45 FCN 950 - 22 1 2 3 5 6 7 8 9 10 11 12 DOK - IBA A 1 2 3 4 5 6 7 8 9 10 11 12 PT 110V Trip 1 Trip 1 Trip 2 Trip 2 INTERNAL DIAGRAM UFR TIPE FCN 950 ABB
CARA SETTING UFR TIPE FCN 950 MERK ABB DC U< 1 2 1 0 f(Hz) dF/dt t(s) SAVE + _ MODE ENABLE 1. Tekan tombol Mode + enable s/d f(Hz) menyala, kemudian tekan tombol Mode + enable s/d lampu 1 (Freq 1) menyala.
2. Untuk menambah / mengurangi nilai setting freq. / waktu dengan cara menekan tombol enable dan tombol + / - .
3. Untuk menyimpan data setting tekan tombol mode + enable s/d lampu save menyala, kemudian tekan tombol enable dan +/- sampai dengan display muncul angka.
DOK - IBA Catatan : 1. Untuk merubah fungsi f(Hz) t(sec) Save 2. Tripping freq. 1 muncul indikasi angka 1.
Tripping freq 2 muncul angka 2.
Tombol enable ditekan terus dan dengan menekan tombol mode maka fungsi akan berubah
DOK - IBA PENGUJIAN INDIVIDUAL RELAI FREKUENSI KURANG TIPE FCN 950 ABB – TEST SET FTS 300 1. TUJUAN Setelah melaksanakan pengujian siswa diharapkan dapat mengukur: 1. pickup / drop off frequency 2. waktu kerja relai frekuensi 2. ALAT UJI / RELAI 1. Frequency Test Set model FTS 300 (EIL) 2. Relai frekuensi tipe FCN 950 ABB 3. RANGKAIAN PENGUJIAN 1. Rangkai lah rangkaian pengujian ( lihat gambar pengujian ) 2. Hubungkan sumber tegangan 220V ke alat uji 3. Posisikan kontrol ( tombol, saklar, alat ukur ) dari alat uji FTS 300 sebagai berikut :
RANGKAIAN PENGUJIAN RELAI FREKUENSI TIPE FCN 950 ABB FTS 300 EIL + CONTACT
-
SUPPLY 220V A NORM. FREQ .
FAULT FREQ.
ON OFF 250V 125V 48V OFF V OUTPUT 7 6 9 8
-
+ UE UE 3 2 1 FCN 950 ABB DOK - IBA PORTABLE TESTSET TIPE FTS 300 EIL RELAI YANG DIUJI
DOK - IBA Kontrol Posisi Main Power switch . . . . . . . .. . . . . . Off Function Switch . . . . . . . . . . . . . Normal Output Voltage adjust control . . . . . . . Putar penuh kekiri Frequency range switch . . . . . . . . . . 40 – 70 Hz Frequency adjust control . . . . . . . . . Mid range Contact mode select switch . . . . . . . . NO (open) Target current range switch . . . . . . . . Sesuai yang diinginkan Target current control . . . . . . . . . . . Putar penuh kekiri DC power supply . . . . . . . . . . . . . . Sesuai yang diinginkan 4. PENGUJIAN PICK UP / DROP OFF FREQUENCY 1. Hidupkan alat uji ( Main power switch pada posisi on ) 2. Putar Output Voltage control ke kanan sampai Voltmeter menunjuk tegangan input nominal relai (100V) 3. Atur normal frequency control sampai frekuensi meter menunjuk harga rated dari normal frekuensi 4. Atur normal frequency control sampai relai mulai pick up ( indikator kontak menyala ) dan naikan frekuensi sampai indikator kontak padam ( reset ) 5. Cata kedua besaran ini , dan ulangi percobaan ini untuk output tegangan yang laian .
DOK - IBA 5. PENGUJIAN WAKTU KERJA RELAI 1. Atur nominal frequency control sehingga frekuensi meter menunjuk harga rated dari normal frekuensi (50Hz) 2. Putar Function swicth ke posisi set fault 3. Atur Fault frequency control sehingga frekuensi meter menunjuk frekuensi yang diinginkan 4. Tekan tombol read voltage control dan atur tegangan gangguan dengan mengatur output voltage control 5. Putar Function switch pada posisi Test maka frekuensi meter akan berubah menjadi Timer (akan mencatat waktu kerja relai ) 6. Ulangi pengujian diatas untuk setting waktu yang lain atau frekuensi gangguan yang lain.
7. Matikan alat uji dan lepas kabel kontrol .
DOK - IBA
KESIMPULAN ;
BANDINGKAN HASIL UJI DENGAN DATA TEKNIK SEHINGGA DIPEROLEH KESIMPULAN BAHWA KONDISI RELAI MASIH STANDAR / NORMAL ATAU MENGALAMI PENURUNAN KUALITAS / CONDONG TIDAK NORMAL DAN PERLU PENGGANTIAN .